TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section6 Page34SCCInc.
Ifacombustionairtemperaturesensorisinstalledandactivated,theairtemperaturewillbe
recordedwhenthelastpointisenteredintotheO
2
ControlCurve.Thistemperatureisstoredunder
thefollowingmenupath:
Params&Display>O2Contr/Alarm>Gas/OilSettings>Startmode>Adjust.TempO2
Thisisthetemperaturethatwillbecomparedagainstthecurrentairtemperaturetoperform
temperaturecompensatedlightoffifparameterStartModeissetto“IgnLoadTC”or“IgnPtWithTC”
(LMV52.440only).
WhenterminalX503.2isproperly configured(seeSection3‐Parameters),itcanbeenergizedto
causeadeactivationoftheO
2
trim.Whenthisisdone,theLMV52willoperateontheO
2
Ratio
ControlCurve.TheO
2
richandleanlimitswillbeactiveaslongasthereisavalidO
2
signal.This
deactivationviaX503.2occurswithoutanotificationbeingdisplayedontheAZL52.
Prepurgemustbesetsothat20.9%(+/‐2.0%O
2
)isreadbytheQGO20sensor.Ifthisisnotmet,a
lockoutordeactivationwilloccurdependingonthesettingofparameterOptgMode.
WhenusingtheLMV52.440onloworultralowNOxmeshburners,aStartModeof“IgnPtWithTC”is
typicallyusedcombinedwithadjustingO2InitOffsetinthenegativedirection(morerich).Ifdone
properly,thisshouldmakethetransitionfromlightoffpositiontolowfirericherthannormal
operationsothatthetransitionisstableandreliableundervaryingenvironmentalconditions.
While
theburnerisbeingheldatPoint2awaitingNumberTauSuspendtoexpire,theO2InitOffsetwill
graduallydissolveandthe%O
2
willbetrimmedtosetpointbeforetheburnerisreleasedto
modulate.
TheAGOgascollectorshouldbemountedpertherequirementsshownbelow: