LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page5 Section7
CANbusFaultsIncludingAZLnotonBusandSystemTest(continued)
MakesuretheshieldingoftheCANbuscableisgroundedproperly.Theshieldingof
theCANbuscableisimmediatelyundertheplasticsheathingandencirclesallfive
conductors.TheshieldingonallsegmentsoftheCANbuscablemusthavecontinuity
withterminalX51.1.Thiscanbecheckedwithamultimeterbyconnectingone
probeontheAGG5.110shieldingclipattachedtoterminalX51.1,andtheother
probeonthelastactuator(orO
2
module)ontheCANbusnetwork.
Ifeverythingelsechecksout,andeverytimeoneoftheactuatorsispluggedinit
immediatelycausesaCANbusfault,replacetheappropriateactuator.