LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 27 Section 1
1-4: Important Safety Notes
The LMV5 is a safety d
evice. Under no circumstances should the unit be modified or
opened. SCC Inc. will not assume responsibility for damage resulting from unauthorized
modification of the unit.
After commissioning, and after each service visit, the flue gas values should be checked
across the firing range.
All activities (mounting, installation, service work, etc.) must be performed by qualified
staff.
Before performing any work in the connection area of the LMV5, disconnect the unit
from the main supply (all-polar disconnection).
Protection against electrical shock hazard on the LMV5 and all other connected
electrical components must be ensured through good wiring and grounding practices.
Fall or shock can adversely affect the safety functions of an LMV5. Such units must not
be put into operation, even if they do not exhibit any apparent damage.
The coupling that is used between the actuator and the driven valve / damper is safety
related, and must be of a robust and flexible design. Should this coupling fail during
operation, the LMV5 will no longer have control of the burner’s combustion, bringing
about a hazardous condition.
Condensation and the entry of water into the unit must be avoided.