LMV Series    Technical Instructions 
  Document No. LV5-80
00 
SCC Inc.  Page 15  Appendix A 
Low Fire Hold with an RWF55 (continued) 
 
Procedure – Steam Boiler with an RWF55 with 
Analog Output 
 
In the case of steam boilers, temperature sensors located in the boiler water jacket are 
recommended.  Technical Instructions SEN-1000 provides additional information on 
temperature sensors. 
1.  Set the following parameters in the LMV5: 
 
Params & Display > LoadController > Configuration > LC_OptgMode = ExtLC X62 
Params & Display > LoadController > Configuration > Ext Inp X62 U/I = 0..20 mA 
 
2.  Set the following parameters in the RWF55: 
 
ConF > Inp > Inp1 > SEn1 = signal type of pressure sensor 
ConF > Inp > Inp1 > SCL1 = 0 
ConF > Inp > Inp1 > SCH1 = high end of the range of the pressure sensor 
ConF > Inp > Inp3 > SEn3 = type of RTD being used for a belly sensor 
ConF > Cntr > CtYP = 2 
ConF > AF > FnCt = 11 
ConF > AF > AL = temperature to enable low fire hold 
ConF > AF > HYSt = deadband around low fire hold temperature 
ConF > OutP > FnCt = 4 
ConF > OutP > SiGn = 0 
 
3.  Wire the LMV5 and RWF55 as shown in Figure 4: 
 
 
 
 
Figure 4:  Low Fire Hold via Analog Output on a Steam Boiler 
 
See page 19 for an example of the
 low fire hold operation.