EasyManua.ls Logo

Siemens MD-BMS - Page 116

Siemens MD-BMS
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendices
Appendix L
-
Core Measurement Parameters
-
Energy
116
Building Technologies 125-202
06/06/2017
Measurement Parameters: Energy BACnet
Object
Identifier
Modbus
Register
Modbus
Offset
(Offset to a
Base of 40001)
kVAh Apparent Energy defined as Kilovolt-Ampere-Hours
is a measure of apparent energy. if the power factor has been constant (1.0) during the time period of metering (measuring) the load, then
kVAh * Power Factor = kWh, or kWh/kVAh= Average PF. kVAh is primarily metered and used by utility suppliers for various billing uses based
upon the user's average power factor; often a concern of industrial applications.
System Total Apparent Energy (kVAh System)
= unsigned value of ABS(kVAh L1)+ABS(kVAh L2)+ABS(kVAh L3), in kVAh
= kVAh Sys, signed, absolute, in kW, BACnet
= kVAh Sys value, unsigned, total instantaneous true energy, in kVAh
= positive kVAh Sys, unsigned, positive instantaneous true energy, in kVAh
= negative kVAh Sys, unsigned, negative instantaneous true energy, in kVAh
NOTES:
If kVAh sys value>0, kVAh sys pos = kVAh sys, kVAh sys neg = 0
If kVAh sys value<0, kVAh sys neg = kVAh sys, kVAh sys pos = 0
7000
7001
7002
44011 lsw
44012 msw
46011 lsw
46012 msw
47011 lsw
47012 msw
4010 lsw
4011 msw
6010 lsw
6011 msw
7010 lsw
7011 msw
Individual Phase Apparent Energy- L1 (kVAh L1)
= kVAh L1 value, signed, individual L1 kVAh energy in kVAh, BACnet
= kVAh L1 value, unsigned, individual L2 kVAh energy, in kVAh
= positive kVAh L1 value, unsigned, individual L2 kVAh energy, in kVAh
= negative kVAh L1 value, unsigned, individual L2 kVAh energy, in kVAh
NOTES:
If kVAh L1 value>0, pos kVAh L1 = total kVAh L1, neg kVAh L1 = 0
If kVAh L1 value<0, neg kVAh L1 = total kVAh L1, pos kVAh L1 = 0
7020
7030
44041 lsw
44042 msw
46041 lsw
46042 msw
47041 lsw
47042 msw
4040 lsw
4041 msw
6040 lsw
6041 msw
7040 lsw
7041 msw
Individual Phase Apparent Energy- L2 (kVAh L2)
= kVAh L2 value, signed, individual L2 kVAh energy in kVAh, BACnet
= kVAh L2 value, unsigned, individual L2 kVAh energy, in kVAh
= positive kVAh L2 value, unsigned, individual L2 kVAh energy, in kVAh
= negative kVAh L2 value, unsigned, individual L2 kVAh energy, in kVAh
NOTES:
If kVAh L2 value>0, pos kVAh L2 = total kVAh L2, neg kVAh L2 = 0)
If kVAh L2 value<0, neg kVAh L2 = total kVAh L2, pos kVAh L2 = 0)
7050
7060
44043 lsw
44044 msw
46043 lsw
46044 msw
47043 lsw
47044 msw
4042 lsw
4043 msw
6042 lsw
6034 msw
7042 lsw
7043 msw
Individual Phase Apparent Energy- L3 (kVAh L3)
= kVAh L3 value, signed, individual L3 kVAh energy in kVAh, BACnet
= kVAh L3 value, unsigned, individual L2 kVAh energy, in kVAh
= positive kVAh L3 value, unsigned, individual L2 kVAh energy, in kVAh
= negative kVAh L3 value, unsigned, individual L2 kVAh energy, in kVAh
NOTES:
If kVAh L3 value>0, pos kVAh L3 = total kVAh L3, neg kVAh L3 = 0
If kVAh L3 value<0, neg kVAh L3 = total kVAh L3, pos kVAh L3 = 0
7080
709
44045 lsw
44046 msw
46045 lsw
46046 msw
47045 lsw
47046 msw
4044 lsw
4045 msw
6044 lsw
6045 msw
7044 lsw
7045 msw

Table of Contents