EasyManua.ls Logo

Siemens MD-BMS - Appendix C - Connecting Multiple MD Power Meters to an RS-485 Network; Communication Protocol; Daisy Chain Layout for RS-485 Network; Networking Using the Bacnet Ms;Tp;Modbus RTU Protocol

Siemens MD-BMS
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendices
Appendix C
-
Connecting Multiple MD Power Meters to an RS
-
485 Network
91
Building Technologies 125-202
06/06/2017
Appendix C - Connecting Multiple MD Power Meters to an
RS-485 Network
This section describes setting up a network with multiple MD-BMS or MD-BMED
Power Meters using the BACnet or Modbus communication protocol. An RS-485
network can support up to 127 MD-BMS or MD-BMED devices using the BACnet
protocol and 247 MD-BMS or MD-BMED devices using the Modbus protocol. Due to
typical BAS network traffic, it is suggested to limit the BACnet devices to less than 100
meters on a network and Modbus devices to less than 150 meters on a network. This
estimation is for sizing only; more meters may be possible depending on control
system network traffic.
Communication Protocol
BACnet MS/TP and Modbus RTU are standard communication protocols that allow
communication between a client and multiple devices connected to the same network.
RS-485 is the protocol standard used by MD-BMS or MD-BMED meters as the
hardware’s physical interface while BACnet or Modbus is the networking protocol.
Daisy Chain Layout for RS-485 Network
When multiple devices are connected, the devices must be connected in a daisy chain.
A daisy chain means that all plus (+) connections are chained together, and all minus (-
) connections are chained together across the network.
A network containing multiple devices requires a unique address for each device. This
allows the master device to identify and communicate with each slave. The
BACnet/Modbus network administrator must assign a unique network address to each
MD-BMS or MD-BMED Power Meter using the rotary switches MSB and LSB.
Other network layouts (for example, star) are not recommended when using the RS-
485 standard.
Networking Using the BACnet MS/TP/Modbus RTU
Protocol
1. Install the RS-485 cable on the RS-485 communications terminal block.
2. Set a unique address for each device using the table in
Establishing
Communication Protocol
in the
Prepping for Installation
section.

Table of Contents

Related product manuals