EasyManua.ls Logo

Siemens MD-BMS - CT Wire Lead Polarity; Connecting the Voltage

Siemens MD-BMS
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Connecting the V
oltage
50
Building Technologies 125-202
06/06/2017
4. Repeat Steps 1 through 3 if you are using more than one Rogowski Coil CT.
To connect the CT's wires to the terminals on the MD-BMS or MD-BMED:
1. Connect the CT's brown wire to the negative terminal on the connector.
2. Connect the CT's white wire to the positive terminal on the connector.
3. Connect the bare shield wire from the Rogowski Coil to the ā€œSā€ shield terminal that
is part of the connector. This reduces interference and improves the accuracy of
the CT.
CT Wire Lead Polarity
Table 13: CT Polarity.
CT Type CT Lead + CT Lead -
Rogowski Coil* White Brown
Split Core mV White Black
* Rogowski Coils have a shield wire that must be connected to the meter. This reduces
interference and improves the accuracy of the CT.
The directionality for Rogowski Coil CTs is that the arrow points t
oward the load (for
example, motor).
Connecting the Voltage
1. Connect the voltage leads (L1, L2, and L3, as necessary) to a circuit breaker. A
voltage lead of 14 AWG THHN Minimum 600 Vac rating (or equivalent, to maintain
600 Vac safety rating of the device) is required.
2. Connect the meter's L1, L2, and L3 leads to the circuit breaker or fuses.
3. See
Wiring Diagrams
for wiring connection specifics. Follow local electrical codes
during installation.

Table of Contents

Related product manuals