Appendices
Appendix L
-
Core Measurement Parameters
-
Energy
115
Building Technologies 125-202
06/06/2017
Appendix L - Core Measurement Parameters - Energy
Measurement Parameters: Energy BACnet
Object
Identifier
Modbus
Register
Modbus
Offset
(Offset to a
Base of 40001)
kWh Real Energy defined as Kilowatt-hour
is a unit of energy equivalent to one kilowatt (1 kW) of power expended for one hour (1 h) of time. The kilowatt-hour is not a standard unit in
any formal system, but it is commonly used in electrical applications. The consumption of electrical energy by homes and small businesses is
usually measured in kilowatt-hours.
System Total True Energy (kWh System)
calculated as ABS(kWh L1) + ABS(kWh L2) + ABS(kWh L3), in kWh
= kWh Sys, signed, absolute, in kWh, BACnet
= total kWh Sys value, unsigned, total instantaneous true energy, in kWh
= positive kWh Sys, unsigned, positive instantaneous true energy, in kWh
= negative kWh Sys, unsigned, negative instantaneous true energy, in kWh
NOTES:
If kWh sys value>0, kWh sys pos = kWh sys, kWh sys neg = 0
If kWh sys value<0, kWh sys neg = kWh sys, kWh sys pos = 0
2000
2010
2020
44001 lsw
44002 msw
46001 lsw
46002 msw
47001 lsw
47002 msw
4000 lsw
4001 msw
6000 lsw
6001 msw
7000 lsw
7001 msw
Individual Phase Instantaneous True Energy- L1 (kWh L1)
= kWh L1 value, signed, individual L1 phase true energy in kWh, BACnet
= kWh L1 value, unsigned, individual L2 phase true energy, in kWh
= positive kWh L1 value, unsigned, individual L2 phase true energy, in kWh
= negative kWh L1 value, unsigned, individual L2 phase true energy, in kWh
NOTES:
If kWh L1 value>0, positive kWh L1 = total kWh L1, negative kWh L1 = 0
If kWh L1 Value<0, negative kWh L1 = total kWh L1, positive aPF = 0
1160
2040
2050
44023 lsw
44023 msw
46023 lsw
46024 msw
47023 lsw
47024 msw
4022 lsw
4023 msw
6022 lsw
6023 msw
7022 lsw
7023 msw
Individual Phase Instantaneous True Energy- L2 (kWh L2)
= kWh L2 value, signed, individual L2 phase true energy in kWh, BACnet
= kWh L2 value, unsigned, individual L2 phase true energy, in kWh
= positive kWh L2 value, unsigned, individual L2 phase true energy, in kWh
= negative kWh L2 value, unsigned, individual L2 phase true energy, in kWh
NOTES:
If kWh L2 value>0, positive kWh L2 = kWh L2, negative kWh L2 = 0
If total kWh L2 value<0, negative kWh L2 = kWh L2, positive kWh L2 = 0
1190
2070
2080
44025 lsw
44026 msw
46025 lsw
46026 msw
47025 lsw
47026 msw
4024 lsw
4025 msw
6024 lsw
6025 msw
7024 lsw
7025 msw
Individual Phase Instantaneous True Energy- L3 (kWh L3)
= kWh L3 value, signed, individual L3 phase true energy in kWh, BACnet
= kWh L3 value, unsigned, individual L2 phase true energy, in kWh
= positive kWh L3 value, unsigned, individual L2 phase true energy, in kWh
= negative kWh L3 value, unsigned, individual L2 phase true energy, in kWh
NOTES:
If kWh L3 value>0, positive kWh L3 = kWh L3, negative kWh L3 = 0)
If kWh L3 value<0, negative kWh L3 = kWh L3, positive kWh L3 = 0)
1220
2100
2110
44027 lsw
44028 msw
46027 lsw
46028 msw
47027 lsw
47026 msw
4026 lsw
4027 msw
6026 lsw
6027 msw
7026 lsw
7027 msw