Installation
Verifying In
stallation with ViewPoint Software
62
Building Technologies 125-202
06/06/2017
Use the Register/Object Picker dialog box to search for registers/objects by name. The
selected value is entered on the Read/Write RegistersRead/Set Objects screen.
1. Click Read to see the current value.
2. Enter a new value in the New Value field.
3. Click Write to change to the new value.
4. Click Clear Totals to clear accumulated data.
NOTE:
Accumulated data consists of registers/objects with a time reference, such as time
since reset, kWh, demands, and so on.
Resetting BACnet Objects/Modbus Registers
Many of the MD-BMS or MD-BMED objects/registers are real-time values such as
instantaneous watts or power factor. However, some objects are accumulated values
such as kWh, kVARh, kVAh and various Peak Demand (kW) values.
To reset all BACnet accumulated objects at once:
Write to object identifier 10140 “Clear Accumulated Values” current value 1234.0.
To reset all Modbus accumulated registers at once:
Write to register 44066 “Clear Accumulated Measurements” current value 1234.
In ViewPoint, accumulating objects/registers can be reset using the Read/Set or
Read/Write tab.
Click Clear Totals at the bottom of the screen.