Building Technologies User Manual OCI600 74 319 0002 0 c
HVAC Products Setting up the OCI600 with the ACS7.. software 15.07.2005
For each of the 4 inputs, edit the relevant values of the data
points listed below.
For each input, a freely selectable name with a maximum of
16 characters can be entered.
Parameter
value
Description
Signalization The input’s state is indicated, e.g. burner
on or off.
Operating hours It is indicated which state the input has
assumed and how long this state has al-
ready existed. This can be used, for ex-
ample, to acquire a burner’s number of
operating hours.
Service For service purposes, all alarms are sup-
pressed.
Alarm at the
time of occur-
rence
When the input is activated, an alarm is
automatically delivered to the associated
alarm receiver.
Alarm at the
time of occur-
rence and dis-
appearance
The input is used as an alarm input.
Each signal change "Active > Inactive",
or vice versa, at the input leads to an a-
larm transmission.
Parameter
value
Description
Normal The input is inactive when the contact is
open (NO).
Inverted The input is inactive when the contact is
closed (NC).
For the inputs parameterized as alarms, select the phone
number to which the alarm message shall be sent.
Alarm messages can be delivered to 4 different numbers in
various combinations.
Each input can be assigned to 1 of the 2 “Outputs OCI600“.
Data point:
“Input n name“
Data point:
“Input n type“
Data point:
“Input n
polarity“
Data point:
“Input n call“
Data point:
“Input n relay“