Mounting Instructions
²
The physical dimensions of the relay and the required cut-out dimensions are shown in 2.1 Drilling
Patterns and Device Dimensions.
²
Insert the rear-side of relay into the RMU/Low Voltage (LV) compartment cut-out.
²
Fasten the relay with 4 M4x20 Pan Phillips SS screws and nuts provided in the 7SR46 packing box. Use a
torque of 0.5 Nm to 0.6 Nm.
²
Carry out all other installation steps and wiring connections from the LV compartment.
²
In the rear side of the relay, execute the wiring process as mentioned in the terminal diagram. Refer to
7SR46 Terminal/Wiring Diagram, Page 28 for more information.
Refer to 2.5 Connectors and Terminal Blocks Specification for the recommended terminal lugs to be
used.
²
The grounding cable must be wired as indicated in 7SR46 Terminal/Wiring Diagram, Page 28 using a
non-stranded cable of 4 mm
2
/6 mm
2
This cable must be terminated in the shortest possible path to the protective grounding terminal or
busbar in the LV compartment.
²
To ensure safety and accidental touch of terminals, maintain a minimum clearance from the relay.
For more details about the minimum clearance, refer to 2.1 Drilling Patterns and Device Dimensions.
If the working area is restricted in a cubicle, then suitable protective terminals must be provided in the
cubicle.
i
i
NOTE
The ground connection of relay casing must be solidly connected to the panel ground.
2.2
Installing the Device
2.2 Mounting Instructions
24 Reyrolle, Operating, Manual
C53000-B7040-C103-1, Edition 10.2022