Troubleshooting
This section provides the common problems of 7SR46 Argus relay and the recommended solution to resolve
the problem.
Observations Action
Relays will not communicate in a ring
network
•
Check that all relays are powered up with auxiliary power
supply.
•
Check that all relays have unique addresses.
•
In self-powered mode, check CT input current above
1.62 ⋅ I
smin
(1-phase) or 0.6 ⋅ I
smin
(3-phase).
Relay Does Not Power Up
•
Check whether correct auxiliary AC or DC voltage is applied,
and the polarity is correct.
•
Check whether phase connections are based on the terminal
diagram and if CT power is applied.
•
Check the USB port if the relay is connected with USB power
•
Check the battery healthy voltage if the relay is powered
with battery power.
Relay Does Not Accept The Password
•
The password entered is wrong. Enter the correct password.
•
If correct password is forgotten, note down the numeric
code displayed at the Change Password screen.
•
To retrieve the password, communicate this numeric code to
a Siemens customer care representative.
HEALTHY LED OFF/LCD Not Displaying
•
In the absence of auxiliary voltage, check the minimum
phase currents.
•
Check the error messages and the error codes under IRF in
the INSTRUMENT MODE.
Binary Inputs Do Not Work
•
Check that the correct BI voltage is applied, and that the
polarity is correct.
•
Check that the binary input settings such as the pick-up and
drop-off timers and the status inversion function are
correctly set.
External trip (ET) input does not work
•
Check whether the device is working on CT power or aux
power and ensure that the device is operating in healthy
condition.
•
Short the ET terminals with a resistance wire and ensure that
the line wire resistance is less than or equal to 20 Ω.
Low/Critical Battery Indication
•
Check whether paper strip between battery clip and battery
is removed.
•
Check whether battery is connected to the correct polarity.
•
Check the battery healthy voltage.
Additional Support
If these measures do not lead to the desired result, the support team will help you. Please contact the local
Siemens office or contact customer support:
•
Phone: +49 911 2155 4466
•
Web: www.siemens.com/reyrolle
•
Email: energy.automation@siemens.com
•
Customer support: www.siemens.com/csc