Structure of the Menu
Relay Menu
7SR46 Argus menu structure has the following main modes:
•
Setting Mode
•
Instrument Mode
•
Fault Data Mode
Setting Mode
This mode allows you to view and change settings in the relay.
Instrument Mode
This mode allows you to view the following conditions of the relay:
•
Current
•
Input/output (I/O) status
•
Miscellaneous status
Fault Data Mode
This mode allows you to view fault records.
The relay menus can only be viewed, once the password (confirmation ID) is entered. Further actions are
permitted when the correct password is entered.
When the relay is shipped from the factory, all the stored data is cleared and the confirmation ID is set to
NONE.
Setting Mode
The SETTING MODE is reached by pressing the READ DOWN(▼) or by pressing the ENTER key from the Relay
Home Screen/Identifier Screen.
Once the setting mode is reached, you can navigate into the settings mode submenus.
Each submenu contains the configurable settings of the relay in separate groups. The submenus are accessed
by pressing the ▶ key (TEST/RESET key). Press the ▲ or ▼ keys to scroll through the first and last settings. If the
keys are pressed further from the first and last settings submenu, it exits from the submenu and returns to the
previous menu.
Press the ENTER key to edit the setting value. If the relay setting is password protected, you are prompted to
enter the password. Settings changes are only allowed after the correct password is entered. If an incorrect
password is entered, editing is not permitted. The password is not required to view and navigate to all screens.
When a setting is edited, flashing characters indicate the edit field. Press the ▲ or ▼ key to scroll through the
valid field values. Hold the ▲ or ▼ keys to increase the rate of scrolling. To navigate between the digits of the
setting values, press the TEST/RESET▶ key.
Once you update the setting, press the CANCEL key to return to the Relay Identifier Screen. The LCD displays
the Save & Restart prompt message. Press ENTER to store the setting in non-volatile memory and the relay
restarts. Press the CANCEL key to discard the changed settings.
Instrument Mode
The instrument mode submenu displays the current values, status of binary inputs, external trip input, and
binary outputs. The following meters are available and can be navigated by using the ▲, ▼, and ▶ keys.
4.4
4.4.1
4.4.2
4.4.3
Using the Device Fascia
4.4 Structure of the Menu
42 Reyrolle, Operating, Manual
C53000-B7040-C103-1, Edition 10.2022