Table 4-2 Instrument Mode
Instrument Description
CURRENT METER
→ to view
This subgroup includes all the meters that are associated with
current.
▶ key allows you to access the subgroup.
The value of current refresh at every 1-s interval.
Primary Current
I
a
0.00A
I
b
0.00A
I
c
0.00A
I
n
0.00A
Displays the primary values of 3 phase currents and derived earth
currents.
Nominal Current
I
a
0.00 * I
s
I
b
0.00 * I
s
I
c
0.00 * I
s
I
n
0.00 * I
s
Displays the primary values of 3 phase currents and derived earth
currents in terms of I
s
.
2ndHarm. Current
I
a
0.000A
I
b
0.000A
I
c
0.000A
Displays the second harmonics values of 3 phase currents.
BINARY I/P METER
→ to view
Binary input meter displays the status of the binary input signals.
The ▶ key allows you to access the subgroup.
The value of binary input status refreshes at every 1-s interval.
BI 1-2
_ _
Displays the state of the binary inputs 1 to 2.
If the status is _, the value is 0. If the status is 1, the value is 1.
ET I/P METER
External trip input meter displays the status of the external trip
input (ETI) signals. As ETI works on scanning principle (5 s OFF /
1 s ON), the value of ETI takes at most 5 s to update.
ET 1
_
Displays the state of the external trip input 1.
If the status is _, the value is 0. If the status is 1, the value is 1.
BINARY O/P METER
→ to view
Binary output meter displays the status of the binary output
signals.
▶ key allows you to access the subgroup.
The value of BO status refreshes at every 1-s interval.
BO 1-2
_ _
Displays the state of the binary outputs 1 to 2.
If the status is _, the value is 0. If status is 1, the value is 1.
GEN ALARM METER
→ to view
The general alarm meter displays the status of the general
alarms.
The ▶ key allows you to access the subgroup.
The general alarm status refreshes at every 1-s interval.
ALARM1 Cleared
ALARM2 Cleared
ALARM3 Cleared
Displays the state of general alarms 1 to 3.
The alarm can be renamed in the settings menu and the updated
name appears in this window.
The status can be Cleared or Raised depending on the binary
input linked to the general alarm.
Using the Device Fascia
4.4 Structure of the Menu
Reyrolle, Operating, Manual 43
C53000-B7040-C103-1, Edition 10.2022