[sc_events_faults, 1, --_--]
You will find additional information about deleting and saving logs in 6.8.2 Saving and Deleting the Logs.
Displaying Indications
Displayed indications in Reydisp and on the on-site operation panel are supplemented with the following
information:
Table 6-5
Overview of Additional Information
Indications in Reydisp Information Device Display Information
Log for operational indications Time stamp (date and time),
Function type,
Function action,
Function description
-
Log for fault indications Entry number
Time stamp (date & time)
Settings group number
Function name
Current values
Entry number
Time stamp (date & time)
Settings group number
Function name
Current values
Resetting Stored Indications
Reset from Relay Fascia
Pressing the key (TEST/RESET key) activates all LEDs (LED test). When released, all stored indications, stored
LEDs, output contacts, and fault displays are reset.
Reset via Binary Inputs
Reset by binary input Rst LEDs & O/Ps switches on all LEDs (LED Test). When the signal reverts, all stored
indications, stored LEDs, output contacts, and fault indications are reset.
6.7.3
6.7.4
In Service Operation
6.7 Indications
Reyrolle, Operating, Manual 63
C53000-B7040-C103-1, Edition 10.2022