Certification
6.1.14Other Approvals
6.1.14 Other Approvals
This device meets the requirements of the following additional standards:
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61850-3
General Requirements
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RX1400 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Test Description Test Levels Severi-
ty Levels
Enclosure Contact ± 8 kVIEC 61000-4-2 ESD
Enclosure Air ± 15 kV
4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m
Signal Ports ± 4 kV @ 2.5 kHz, 5 kHz
Note
a
DC Power Ports ± 4 kV @ 2.5 kHz, 5 kHz
AC Power Ports ± 4 kV
IEC 61000-4-4 Burst (Fast Transient)
Earth Ground Ports ± 4 kV @ 2.5 kHz, 5 kHz
4
Signal Ports ± 4 kV Line-to-Earth
± 2 kV Line-to-Line
DC Power Ports ± 2 kV Line-to-Earth
± 1 kV Line-to-Line
3
IEC 61000-4-5 Surge Immunity
AC Power Ports ± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6 Induced (Conducted) RFI
Earth Ground Ports
10 V 3
IEC 61000-4-8 Magnetic Field Enclosure Ports 100 A/m Continuous 5
54
RUGGEDCOM RX1400
Installation Manual, 09/2019, C79000-G8976-1103-13

Table of Contents

Other manuals for Siemens RUGGEDCOM RX1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RX1400 and is the answer not in the manual?

Siemens RUGGEDCOM RX1400 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RX1400
CategoryNetwork Hardware
LanguageEnglish

Related product manuals