EasyManuals Logo

Siemens RUGGEDCOM RX1400 User Manual

Siemens RUGGEDCOM RX1400
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels
IEEE 1613.1/
IEC 61000-4-10
Damped Oscillat-
ing Magnetic Field
Enclosure Ports 100 A/m for 1 s (100 kHz and 1 MHz)
Environmental Type Tests
Test Description Test Levels
Cold Temperature Test Ad -40 °C (-40 °F), 16 HoursIEC 60068-2-1
Cold Storage Test Ab -40 °C (-40 °F), 16 hours
Dry Heat Test Bd 85 °C (185 °F), 16 HoursIEC 60068-2-2
Dry Heat Storage Test Bb 85 °C (185 °F), 16 hours
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db 95% (Non-Condensing),
55 °C (131 °F), 6 cycles
IEC 60068-78 Humidity (Damp Heat, Steady State) 10 days @ 55 °C (131 °F)
and 93% Relative Humidity
IEC 60255-21-1 Vibration 2 g @ 10-150 Hz
IEC 60255-21-2 Shock 30 g @ 11 ms
IEC 60255-21-3 Seismic Method A, Class 2
IEC 60068-1-14 Change of Temperature 5 Cycles (-40 to 85 °C or -40 to 185 °F)
56
RUGGEDCOM RX1400
Installation Manual, 09/2019, C79000-G8976-1103-13

Table of Contents