S5-100U STEP 5 Operations
Table 8-3. Overview of Load and Transfer Operations
1
These operands cannot be used for transfer.
* Programmer dependent
Opera-
tion
MeaningOperand
Load
The operand contents are copied into ACCU 1 regardless of the RLO.
The RLO is not affected.
L
Transfer
The contents of ACCU 1 are assigned to an operand regardless of the
RLO.
The RLO is not affected.
ID
IB
IW
QB
QW
FY
FW
DR
DL
DW
T
1
C
1
PB/PY*
PW
KM
1
KH
1
KF
1
KY
1
KB
1
KS
1
KT
1
KC
1
T
Parameter CPU 100 CPU 102 CPU 103
0 to 15 0 to 31 0 to 127
0 to 15 0 to 31 0 to 127
ID
T
C
LD Load in BCD
Binary times and counts are loaded into ACCU 1 in BCD code regardless
of the RLO.
Parameter
CPU 100 CPU 102 CPU 103
0 to 127 0 to 127 0 to 127
0 to 126 0 to 126 0 to 126
0 to 127 0 to 127 0 to 127
0 to 126 0 to 126 0 to 126
0 to 127 0 to 127 0 to 255
0 to 126 0 to 126 0 to 254
0 to 255 0 to 255 0 to 255
0 to 255 0 to 255 0 to 255
0 to 255 0 to 255 0 to 255
0 to 15 0 to 31 0 to 127
0 to 15 0 to 31 0 to 127
----- ----- 0 to 127
----- ----- 0 to 126
random bit random bit random bit
pattern (16 bits) pattern (16 bits) pattern (16 bits)
0 to FFFF 0 to FFFF 0 to FFFF
-32768 to+32767 -32768 to +32767 -32768 to +32767
0 to 255 0 to 255 0 to 255
per byte per byte per byte
0 to 255 0 to 255 0 to 255
any 2 any 2 any 2
alphanumeric alphanumeric alphanumeric
characters characters characters
0.0 to 999.3 0.0 to 999.3 0.0 to 999.3
0 to 999 0 to 999 0 to 999
EWA 4NEB 812 6120-02
8-11