EasyManua.ls Logo

Siemens S5-100U - 3.1.2 Multi-Tier Expansion

Siemens S5-100U
512 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S5-1OOU
Installation Guidelines
3.1.2 Multi-Tier Expansion
-.
If it is not possible to have all of the modules located on one tier, you can expand the configuration
up to four tiers. You may use a maximum of 16 bus units.
It does not matter how many bus units
are mounted on a tier. You need one interface module per tier to interconnect the tiers.
Install an interface module as you would install a bus unit. You must connect each interface module
to the last bus unit via the ribbon cable.
Use the
IM
315 interface module for two-tier configurations.
The
IM
315 consists of two modules
permanently connected to each other via a 0.5-m (20-in. ) cable.
Use the
IM
316 interface modules for multi-tier configurations.
Use the 712-8 connecting cable to
connect the
IM
316 interface modules (Order No. 6ES5 712-8...).
The standard mounting rails must have a common reference potential if they are mounted in
different cabinets.
Figure 3-4. Interconnecting Tiers with Interface Modules
(6ES5
316-8 MA12)
EWA 4NEB 8126120-02
3-5