S5-100U Module Spectrum
14 Module Spectrum
14.1 General Technical Specifications
Temperature
Operating
- horizontal design 0 to+60° C (32 to 140° F)
- vertical design 0 to+40° C (32 to 104° F)
(Air-intake temperature,
measured on the underside
of the module)
Nonoperating - 40 to +70° C
(- 40 to +150° F)
Temperature change
- operating max. 10° C/h (50° F/h)
- nonoperating max. 20° C/h (68° F/h)
Relative humidity to DIN 40040
15 to 95% (indoors),
noncondensing
Atmospheric pressure
- operating 860 to 1060 hPa
- nonoperating 660 to 1060 hPa
Pollutants
-SO
2
0.5 ppm,
(rel. humidity 60%,
noncondensing)
-H
2
S 0.1 ppm,
(rel. humidity 60%,
noncondensing)
Climatic Environmental Conditions
Electromagnetic Compatibility (EMC)
Noise Immunity
Mechanical Environmental Conditions
Vibration to IEC 68-2-6
- tested with 10 to 57 Hz,
(const. ampl. 0.15 mm)
57 to 150 Hz,
(const. accel. 2 g)
Shock to IEC 68-2-27
- tested with 12 shocks
(semisinusoidal
15 g /11 ms)
Free-fall to IEC 68-2-31
- tested with height of fall 50 mm
Radiated electromagnetic to IEC 801-3
field test field strength 3 V/m
Fast transient burst to IEC 801-4,
class III
Power supply
modules
- Supply voltage 24 V DC 1 kV
- Supply voltage 115/230 V AC 2 kV
- Analog input/output modules 1 kV
- Digital input/output modules
for V = 24 V 1 kV
for V > 24 V 2 kV
Communications
interface 1 kV
Electromagnetic Compatibility (EMC)
Noise Immunity
Electrostatic discharge to IEC 801-2
test (Discharge on all parts that
are accessible to the oper-
ator during normal operation)
- Test voltage 2.5 kV
(rel. humidity
30 to 95%)
IEC/VDE Safety Information
Degree of protection to IEC 529
- Type IP 20
- Class to IEC 536
Insulation rating to VDE 0160
- between electrically (05. 1988)
independent circuits
and
with circuits connected
to a central grounding
point to VDE 0160
- between all circuits (05. 1988)
and
a central grounding point
(standard mounting rail) to VDE 0160
(05. 1988)
Test voltage sine, 50 Hz
for a rated voltage
V
input
of the circuits (AC/DC)
V
input
= 0 to 50 V 500 V
V
input
= 50 to 125 V 1250 V
V
input
= 125 to 250 V 1500 V
EWA 4NEB 812 6120-02
14-1