S5-100U The Integral Real-Time Clock
FB11 STL (continued) Description
:L =HOUR STORE VALUE FOR HOURS
:ON =AMPM IF AM/PM = 1 (AFTERNOON) AND
:ON =MODE 12-HOUR MODE IS SET, THE
:JC =MORN CORRESPONDING BIT IN THE CLOCK
:L KH 0080 DATA AREA IS SET
:OW
MORN :T DR 10
:L =MIN STORE VALUE FOR MINUTES
:T DL 11
:L =SEC STORE VALUE FOR SECONDS
:T DR 11
:AN F 10.6 TRANSFER SETTINGS
:S F 10.6 (BIT 14 IN STATUS WORD FW10)
:L KT 020.1 START MONITORING TIME
:SE T 11
M001 :A T 11 BEC, IF MONITORING TIME NOT YET
:BEC ELAPSED
:AN F 10.6 HAVE SETTINGS BEEN TRANSFERRED?
:JC =M002 IF YES, JUMP TO M002
:S =ERR IF ERROR, SET ERROR BIT
:BEU
M002 :AN F 10.4 ERROR WHEN ENTERING SETTINGS?
:RB =ERR IF NO, RESET ERROR BIT
:BEC BEC, IF NO ERROR
:S =ERR IF ERROR, SET ERROR BIT
:BE
EWA 4NEB 812 6120-02
12-29