Technical specifications
Address designation
(for ET 100U only) 8 DQ
Outputs 8 relay outputs,
contact switching
varistor SIOV-
S07-K275
Galvanic isolation yes
- in groups of 2 with signal
status display
Continuous current I
th
3 A
Relay type Dold OW 5699
Switching capacity
of the contacts
- resistive load max. 3 A at 250 V AC
1.5 A
at 30 V DC
- inductive load max. 0.5
A at 250 V AC
0.5 A at 30 V DC
Operating cycles of
the contacts according to
VDE 0660, part 200
- AC - 11 1 x 10
6
- DC - 11 0.5 x 10
6
Switching frequency max. 10 Hz
Fault LED (red) no input voltage
Permissible ambient
temperature of module
- horizontal arrangement 0 to 60 °C
(32 to 140 °F)
- vertical arrangement 0 to 40 °C
(32 to 104 °F)
Length of cable
- unshielded max. 100 m (330 ft.)
Insulation rating VDE 0160
Rated insulation voltage
(+ 9 V to L 1) 250 V AC
- insulation group 2 x B
- tested with 1500 V AC
Rated insulation voltage
(+ 9 V to ) 250 V AC
- insulation group 1 x B
- tested with 500 V AC
Rated insulation voltage
(between contacts) 12 V AC
- insulation group 2 x B
- tested with 1500 V AC
Supply voltage L+
(for the relay)
- rated value 24 V DC
- ripple V
PP
max. 3.6 V
- permissible range
(ripple included) 20 to 30 V
- value to t <0.5 s 35 V
Current consumption
- from + 9 V (CPU) typ. 30 mA
- from L+ typ. 70 mA
Power loss
of the module typ. 1.6 W
Weight approx. 300 g (11 oz.)