Technical specifications
SCALANCE X-200
Operating Instructions, 03/2015, C79000-G8976-C284-06
71
Permitted cable lengths - copper
For devices with degree of protection IP20/30
The following cables are permitted in the specified lengths:
0 to 55 m:
IE TP torsion cable with IE FC RJ-45 Plug 180
Alternative:
0 to 45 m IE TP Torsion Cable + 10 m TP Cord via IE Outlet RJ-45
0 to 85 m:
IE FC TP marine / trailing / flexible / FRNC / festoon / food cable with IE FC RJ-45 Plug
180
Alternative:
0 to 75 m IE FC TP marine / trailing / flexible / FRNC / festoon / food cable + 10 m TP
cord over IE FC outlet RJ-45
0 to 100 m:
IE FC TP standard cable with IE FC RJ-45 plug 180
Alternative:
0 to 90 m IE FC TP standard cable + 10 m TP cord via IE FC outlet RJ-45
For devices with the "PRO" supplement (degree of protection IP65/67)
With these devices, splitting of the cables (as above) is not permitted. The following cables
are permitted in the specified lengths:
0 to 55 m:
IE TP torsion cable with IE FC RJ-45 Plug 180
0 to 85 m:
IE FC TP marine / trailing / flexible / FRNC / festoon / food cable with IE FC RJ-45 Plug
180
0 to 100 m:
IE FC TP standard cable with IE FC RJ-45 plug 180