Appendix
A.1 Modbus TCP
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
107
File
(FC0x14)
Offset
address
Address
FC0x03
FC0x04
Number
of
registers
Name
Format
Unit
Value range
Access
2
277
31277
2
Maximum current L3
Float
A
R
R
2 279 31279 2 Maximum apparent pow-
er L1
Float VA R R
2 281 31281 2 Maximum apparent pow-
er L2
Float VA R R
2 283 31283 2 Maximum apparent pow-
er L3
Float VA R R
2
285
31285
2
Maximum active power L1
Float
W
R
R
2
287
31287
2
Maximum active power L2
Float
W
R
R
2
289
31289
2
Maximum active power L3
Float
W
R
R
2 291 31291 2 Maximum reactive pow-
er L1
Float var R R
2 293 31293 2 Maximum reactive pow-
er L2
Float var R R
2 295 31295 2 Maximum reactive pow-
er L3
Float var R R
2
297
31297
2
Maximum power factor L1
Float
-
R
R
2
299
31299
2
Maximum power factor L2
Float
-
R
R
2
301
31301
2
Maximum power factor L3
Float
-
R
R
2
303
31303
2
Maximum frequency
Float
Hz
R
R
2 305 31305 2 Maximum average voltage
L - N
Float V R R
2 307 31307 2 Maximum average voltage
L - L
Float V R R
2 309 31309 2 Maximum average current Float A R R
2 311 31311 2 Maximum total apparent
power
Float VA R R
2 313 31313 2 Maximum total active
power
Float W R R
2 315 31315 2 Maximum total reactive
power
Float var R R
2 317 31317 2 Maximum total power
factor
Float - R R
2
513
31513
2
Time stamp
unix_ts
-
R
2 515 31515 2 Flags uint32_t - 0= UNFLAGGED
1= FLAGGED
2= SAG
4= SWELL
8= POWER FAIL
R
2
517
31517
2
Minimum voltage L1 - N
Float
V
R
R
2
519
31519
2
Minimum voltage L2 - N
Float
V
R
R
2
521
31521
2
Minimum voltage L3 - N
Float
V
R
R
2
523
31523
2
Minimum voltage L1 - L2
Float
V
R
R

Table of Contents