Appendix
A.1 Modbus TCP
PAC2200
108 Equipment Manual, 12/2019, L1V30415167B-03
File
(FC0x14)
Offset
address
Address
FC0x03
FC0x04
Number
of
registers
Name
Format
Unit
Value range
Access
2
525
31525
2
Minimum voltage L2 - L3
Float
V
R
R
2
527
31527
2
Minimum voltage L3 - L1
Float
V
R
R
2
529
31529
2
Minimum current L1
Float
A
R
R
2 531 31531 2 Minimum current L2 Float A R R
2
533
31533
2
Minimum current L3
Float
A
R
R
2 535 31535 2 Minimum apparent pow-
er L1
Float VA R R
2 537 31537 2 Minimum apparent pow-
er L2
Float VA R R
2 539 31539 2 Minimum apparent pow-
er L3
Float VA R R
2
541
31541
2
Minimum active power L1
Float
W
R
R
2
543
31534
2
Minimum active power L2
Float
W
R
R
2
545
31545
2
Minimum active power L3
Float
W
R
R
2 547 31547 2 Minimum reactive pow-
er L1
Float var R R
2 549 31549 2 Minimum reactive pow-
er L2
Float var R R
2 551 31551 2 Minimum reactive pow-
er L3
Float var R R
2
553
31553
2
Minimum power factor L1
Float
-
R
R
2
555
31555
2
Minimum power factor L2
Float
-
R
R
2
557
31557
2
Minimum power factor L3
Float
-
R
R
2
559
31559
2
Minimum frequency
Float
Hz
R
R
2 561 31561 2 Minimum average voltage
L - N
Float V R R
2 563 31563 2 Minimum average voltage
L - L
Float V R R
2
565
31565
2
Minimum average current
Float
A
R
R
2 567 31567 2 Minimum total apparent
power
Float VA R R
2 569 31569 2 Minimum total active pow-
er
Float W R R
2 571 31571 2 Minimum total reactive
power
Float var R R
2 573 31573 2 Minimum total power
factor
Float - R R