Commissioning
6.3 Parameterizing the device
PAC2200
70 Equipment Manual, 12/2019, L1V30415167B-03
"Date/Time" parameter
The date and time can be set by using the "Date/time" option in the "Settings" menu.
Selection
Range
Factory setting
DATE Current date
The date format is defined in the FORMAT field.
FORMAT DD.MM.YYYY (day month year)
MM/DD/YY (month day – year)
YYYY-MM-DD (year month day)
DD.MM.YYYY
TIME
HH:MM:SS
TIME ZONE Time zone, refers to coordinated universal time (UTC)
12:00 … +14:00, in 30-minute intervals
Examples:
No:
"−06:00" corresponds to UTC-6
Yes:
"+01:00" corresponds to UTC+1
00:00
DAYL.SAVING Automatic change of time from standard time to daylight sav-
ing time and from daylight saving time to standard time.
OFF:
Time change is switched off
Auto EU:
Time change within the European Union, changeover to
daylight saving time: The internal clock is put forward from
1 a.m. UTC to 2 a.m. UTC on the last Sunday in March.
Changeover to standard time: The internal clock is put
back from 2 a.m. UTC to 1 a.m. UTC on the last Sunday in
October.
Auto US:
Time change within the USA,
changeover to daylight saving time: The internal clock is
put forward from 2 a.m. local time to 3 a.m. on the second
Sunday in March. Changeover to standard time: The in-
ternal clock is put back from 2 a.m. local time to 1 a.m. on
the first Sunday in November.
Table:
Time change can be individually parameterized. The pa-
rameters can be set in the software.
OFF