Commissioning
6.3 Parameterizing the device
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
75
"MODBUS RTU" parameter (optional)
The "MODBUS RTU" parameter is only available for devices with an RS485 interface.
Selection
Range
Factory setting
ADDRESS
Range: 1 to 247
126
BAUD RATE
Range: 4800 / 9600 / 19200 / 38400
19200
FORMAT
8N1 / 8N2 / 8E1 / 8O1
8N2
RESPONSE TIME Range: 0 to 255 ms 0 ms
"M-BUS" parameter (optional)
The "M-BUS" parameter is only available for devices with an M-BUS interface.
Selection
Range
Factory setting
PRIMARY ADDRESS
Range: 0 to 250
0
SECONDARY
ADDRESS
The secondary address is generated automatically
from the serial number of the device.
BAUD RATE
1200 / 2400 / 4800 / 9600
9600
"Display" parameter
Selection
Range
Factory setting
CONTRAST The display contrast can be adjusted in steps.
Range: 0 - 10
5
BRIGHTNESS The intensity of the backlighting can be adjusted in
steps.
Range: 0 - 3
3
BACKL.DIMMED The dimming setting of the display can be adjusted in
steps.
Range: 0 - 3
3
DIM AFTER On expiry of the set period, the backlighting is dimmed
to the set intensity.
Range: 0 - 99
3
TEST INDICATOR Display test indicator. For testing the functional capa-
bility of the display.
DEFAULT MENU Menu display number for the default menu. The device
always starts up with the menu display defined here.
Range: 1 - 12
1
TIMEOUT When the specified time has elapsed, the device au-
tomatically returns to the defined default menu.
Range: 0 s - 3600 s (0 = function deactivated)
0