Technical specifications
8.1 Technical specifications
PAC2200
88 Equipment Manual, 12/2019, L1V30415167B-03
Connection elements
The specified conductor cross sections describe the capacity of the connection terminals.
When selecting the conduction cross sections, always pay attention to the possible current
load and ensure adequate cable protection.
Current, power supply
5 A device
65 A device
Conductor cross-section for copper cable (Cu)
Rigid
0.2 ... 6.0 mm
2
[AWG 24...10]
0.75 ... 35 mm²
[AWG 19 ... 2]
Flexible
0.2 ... 4.0 mm²
[AWG 24...12]
1 ... 35mm²
[AWG 18 ... 2]
Flexible with end sleeve, without plastic
sleeve
0.2 ... 4.0 mm²
[AWG 24...12]
0.75 ... 25 mm²
[AWG 19 ... 4]
Flexible with end sleeve and plastic
sleeve
0.25 ... 4.0 m
[AWG 24...12]
0.75 ... 25 mm²
[AWG 19 ... 4]
2-wire, same cross-section
Rigid
0.2 ... 1.5 mm²
[AWG 24 ... 16]
0.75 ... 10 mm²
[AWG 19 ... 8]
Flexible
0.2 ... 1.5 mm²
[AWG 24 ... 16]
1 ... 4mm²
[AWG 18 ... 12]
Flexible with end sleeve, without plastic
sleeve
0.25 ... 0.75 m
[AWG 24 ... 19]
0.75 ... 4 mm²
[AWG 19 ... 12]
Flexible with TWIN end sleeve and plastic
sleeve
0.5 ... 2.5 mm²
[AWG 20 ... 14]
0.75 ... 4 mm²
[AWG 19 ... 12]
Tightening torque 0.5 ... 0.6 Nm
[4.4 ... 5.3 lb-in]
3 Nm
[26.6 lb-in]
Conductor cross-section for copper cable (Cu)
for UL market
AWG 10 ... 4
Solid or stranded with ferrules
Conductor cross-section for copper cable (Cu)
for CSA market
AWG 8 ... 4
Compact stranded