3.5 Three-phase devices 5 A
7KT16 energy meter
62 Equipment Manual, 09/2020, 2514284147-04
P13 Input
Default
Range
P13.01
Input function
OFF
LOCK
TAR-A
C01 … C08
P13.02
Normal status
OFF
ON
P13.03
Delay "ON"
s
1 … 4
P13.04
Delay "OFF"
P13.01
Input function:
OFF = Input deactivated.
LOCK = Settings lock. Prevents access to both levels.
TAR-A = Selects the energy tariff. You can find more information in chapter
Tariffs (Page 51).
C01 … C08 = When this input is activated (during rise time), the corresponding
command is active in the command menu. You can find more information in
chapter Command menu (Page 64).
P13.02
Enter normal status. Permits inversion of activation logic.
P13.03
Delay setting for "ON".
P13.04
Delay setting for "OFF".