Commissioning
6.4 Modbus address register
7KT16 energy meter
88 Equipment Manual, 09/2020, 2514284147-04
Address
Number
of regis-
ters
Format Access Unit Factor Measured variable
Hex Decimal
1E84
7812
4
UINT64
R
Wh
10.0
Partial active energy L3 - Import
1E88
7816
4
UINT64
R
Wh
10.0
Partial active energy L3 - Export
1E8C
7820
4
UINT64
R
varh
10.0
Partial reactive energy L3 - Import
1E90
7824
4
UINT64
R
varh
10.0
Partial reactive energy L3 - Export
1E94
7828
4
UINT64
R
VAh
10.0
Partial apparent energy L3
Hour counter
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format Access Unit Factor Measured variable
Hex Decimal
1E00
7680
2
UINT32
R
s
1.0
Total operating hours counter
1E02
7682
2
UINT32
R
s
1.0
Partial operating hours counter 1
1E04
7684
2
UINT32
R
s
1.0
Partial operating hours counter 2
1E06
7686
2
UINT32
R
s
1.0
Partial operating hours counter 3
1E08
7688
2
UINT32
R
s
1.0
Partial operating hours counter 4
Status
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format Access Unit Factor Measured variable
Hex Decimal
2140
8512
1
UINT16
R
BOOL
OR across all limits *1
2141
8513
1
UINT16
R
BOOL
Limit 1
2142
8514
1
UINT16
R
BOOL
Limit 2
2143
8515
1
UINT16
R
BOOL
Limit 3
2144
8516
1
UINT16
R
BOOL
Limit 4
2145
8517
1
UINT16
R
BOOL
Limit 5
2146
8518
1
UINT16
R
BOOL
Limit 6
2147
8519
1
UINT16
R
BOOL
Limit 7
2148
8520
1
UINT16
R
BOOL
Limit 8
1
Example: If the value (hex) =0x05, inputs 1 and 3 are active.