Commissioning
6.4 Modbus address register
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
89
Address
Number
of regis-
ters
Format Access Unit Factor Measured variable
Hex Decimal
4F00
20224
1
UINT16
R
BOOL
Remote 1
4F01
20225
1
UINT16
R
BOOL
Remote 2
4F02
20226
1
UINT16
R
BOOL
Remote 3
4F04
20227
1
UINT16
R
BOOL
Remote 4
Modbus command parameter
Modbus measured variables with the function code 06
Address
Number
of regis-
ters
Format Access Unit Factor Measured variable
Hex Decimal
2FF0
12272
1
UINT16
W
0
Reset max & min values
UINT16
W
1
Reset max demand values
UINT16
W
2
Reset partial energy counter
UINT16
W
3
Reset partial operating hours counter
UINT16
W
4
Reset external counters
UINT16
W
5
Reset energy tariffs
UINT16
W
6
Reset alarms
UINT16
W
7
Reset limits
UINT16
W
11
Reset total energy
UINT16
W
12
Reset all operating hours counters
UINT16
W
13
Reset parameters to factory default
1)
UINT16
W
14
Backup all parameters
1)
UINT16
W
15
Restore all parameters
1)
UINT16
W
16
Wiring test
2)
UINT16
W
100
Reset maximum values
UINT16
W
200
Reset minimum values
2FF1
12273
1
UINT16
W
1
System restart
Range limit
4200
16896
1
UINT16
W
1, 2
Set active energy tariff
3)
1)
After executing this command, it is recommended that you issue the REBOOT command.
2)
After executing this command, you can use the query under address 0x1F20 to obtain the test result. The assignments
of the reply bit are shown in the wiring test results table below.
3)
This function is only active if none of the inputs is assigned the tariff function (TAR-A and TAR-B).