Appendix
A.1 Modbus TCP
PAC2200
Manual, 05/2018, L1V30415167B-02
99
Table A- 8 Settings parameter for the digital input
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50025 2 Digital input "Action" - unsigned long
0 =
Status only
RW
1 = Pulse input
2 = High tariff / low
tariff switching
3 =
Synchronization
50029 2 "Pulse input" mode kWh unsigned long
0 =
0 kWh
RW
1 =
Export kWh
50031 2 Pulses per unit (pulses
per 1000 Wh / VARh)
- unsigned long 1 ... 4000 RW
50239 2 Input pulse divider kWh unsigned long
0 =
1 kWh
RW
1 =
10 kWh
2 =
100 kWh
3 =
1000 kWh