Appendix
A.1 Modbus TCP
PAC2200
98 Manual, 05/2018, L1V30415167B-02
Modbus settings with the function codes 0x03, 0x04 and 0x10
Addressing the settings
You can use the Modbus function codes 0x03, 0x04 for read accesses and 0x10 for write
accesses on all the settings parameters listed below.
Table A- 7 Settings parameters
49999 2 Rated current display
A unsigned long 1 - 99999 A RW
50001 2 Connection type - unsigned long 0 = 3P4W RW
2)
50011 2 Primary current A unsigned long 1 ... 99999 A (5 A device) RW
50023 2 Synchronization - unsigned long
RW
1 = Synchronization
2 = Synchronization
50243 2 Change current L1 direc-
tion
2)
- unsigned long
RW
50245 2 Change current L2 direc-
tion
2)
- unsigned long
RW
50247 2 Change current L3 direc-
tion
2)
- unsigned long
RW
2) Not available for MID and 65A devices