EasyManua.ls Logo

Siemens SENTRON PAC2200 - Modbus Settings with the Function Codes 0 X03, 0 X04 and 0 X10

Siemens SENTRON PAC2200
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.1 Modbus TCP
PAC2200
98 Manual, 05/2018, L1V30415167B-02
A.1.8
Modbus settings with the function codes 0x03, 0x04 and 0x10
Addressing the settings
You can use the Modbus function codes 0x03, 0x04 for read accesses and 0x10 for write
accesses on all the settings parameters listed below.
Table A- 7 Settings parameters
Offset
Number of
registers
Name
Unit
Format
Value range
Access
49999 2 Rated current display
range
A unsigned long 1 - 99999 A RW
50001 2 Connection type - unsigned long 0 = 3P4W RW
4 =
1P2W
2)
50011 2 Primary current A unsigned long 1 ... 99999 A (5 A device) RW
65 A (65 A device)
R
50013
2
Secondary current
A
unsigned long
1 A, 5 A (5 A device)
RW
65 A (65 A device)
R
50021
2
Demand period
Min.
unsigned long
1 ... 60
RW
50023 2 Synchronization - unsigned long
0 =
No synchronization
RW
1 = Synchronization
via bus
2 = Synchronization
via the digital input
50243 2 Change current L1 direc-
tion
2)
- unsigned long
0 =
No
RW
1 =
Yes
50245 2 Change current L2 direc-
tion
2)
- unsigned long
0 =
No
RW
1 =
Yes
50247 2 Change current L3 direc-
tion
2)
- unsigned long
0 =
No
RW
1 =
Yes
2) Not available for MID and 65A devices

Table of Contents

Related product manuals