Appendix
A.1 Modbus TCP
PAC2200
104 Manual, 05/2018, L1V30415167B-02
A.1.11
Modbus command parameters
Addressing the command parameters
You can apply the Modbus function code 0x06 to the command parameters.
Table A- 13 Command parameters
Offset
Number
of regis-
ters
Name
Unit
Format
Value range
Access
60004 1 Reset energy counter - unsigned short
0 =
all
W
1 = Active energy
import tariff 1
2 = Active energy
import tariff 2
3 = Active energy
export tariff 1
4 = Active energy
export tariff 2
5 = Reactive energy
import tariff 1
6 = Reactive energy
import tariff 2
7 = Reactive energy
export tariff 1
8 = Reactive energy
export tariff 2
9 = Apparent energy
tariff 1
10 = Apparent energy
tariff 2
60005 1 Synchronization of the de-
mand period
Min. unsigned short 1 ... 60 W
60006 1 Switching tariff - unsigned short 0 = Main tariff W
1 = Secondary
tariff
60007 1 Acknowledge the diagnostics
bits
3)
(cf. stored bits in un-
signed long beginning off-
set 205)
- unsigned short 0 ... ffffh W
60008 1 Switching outputs (if parame-
terized)
- unsigned short
0ffh ... 1ffh
W
Byte 0
= 0
Digital output
0.0
Byte 1
= 0
OFF
Byte 1
= 1
ON