Connection
4.1 Safety notes
PAC2200
40 Manual, 05/2018, L1V30415167B-02
DANGER
Open transformer circuits will result in electric shock and arc flashover!
Failure to observe this notice will cause death, serious injury or considerable damage to
property.
For the 5 A device it is only possible to measure the current via external current
transformers. When using the
current transformers, the circuit is not protected by a fuse. Do
not open the secondary circuit of the current transformers under load. Short circuit the
secondary current terminals of the current transformer before removing this device. The
safety information for the current transformers used must be followed.
CAUTION
Protection of the voltage measuring inputs
The fuses in the voltage measuring inputs are only used for cable protection. Selection of
the fuse depends on the supply cable dimensioning. The relevant applicable regulations
must be complied with.
See also
Applying the measuring voltage (Page 58)
Measuring inputs (Page 15)