Appendix
A.1 Modbus TCP
PAC2200
Manual, 05/2018, L1V30415167B-02
93
25 2 Apparent power L2 Float VA R
27
2
Apparent power L3
Float
VA
R
29 2 Active power L1 Float W R
31
2
Active power L2
Float
W
R
33
2
Active power L3
Float
W
R
35
2
Reactive power L1
Float
var
R
37
2
Reactive power L2
Float
var
R
39
2
Reactive power L3
Float
var
R
41
2
Power factor L1
Float
-
R
43
2
Power factor L2
Float
-
R
45
2
Power factor L3
Float
-
R
47
2
Frequency
Float
Hz
R
49
2
Average voltage L - N
Float
V
R
51
2
Average voltage L - L
Float
V
R
53
2
Average current
Float
A
R
55
2
Total apparent power
Float
VA
R
57
2
Total active power
Float
W
R
59
2
Total reactive power
Float
var
R
61
2
Total power factor
Float
-
R
257
2
Time stamp
unix_ts
-
R
259 2 Flags uint32_t - 0= UNFLAGGED
1= FLAGGED
2= SAG
4= SWELL
8= POWER FAIL
R
261 2 Maximum voltage L1 - N Float V R
263
2
Maximum voltage L2 - N
Float
V
R
265
2
Maximum voltage L3 - N
Float
V
R
267
2
Maximum voltage L1 - L2
Float
V
R
R
269
2
Maximum voltage L2 - L3
Float
V
R
R
271
2
Maximum voltage L3 - L1
Float
V
R
R
273
2
Maximum current L1
Float
A
R
R
275
2
Maximum current L2
Float
A
R
R
277
2
Maximum current L3
Float
A
R
R
279
2
Maximum apparent power L1
Float
VA
R
R
281
2
Maximum apparent power L2
Float
VA
R
R
283
2
Maximum apparent power L3
Float
VA
R
R
285
2
Maximum active power L1
Float
W
R
R
287
2
Maximum active power L2
Float
W
R
R
289
2
Maximum active power L3
Float
W
R
R
291
2
Maximum reactive power L1
Float
var
R
R
293
2
Maximum reactive power L2
Float
var
R
R
295 2 Maximum reactive power L3 Float var R R

Table of Contents