1.4 Climatic Ambient Conditions
Parameter Value Test standard Product standard Class
Minimum air temperature
(cold)
-40°C/96 h
IEC 60068-2-1
Ad
IEC 60870-2-2
IEC 60654-1
C2/C3
C2/C3
Maximum air temperature
(dry heat)
70°C/96 h
1)
50°C/96 h
2)
10% rH
IEC 60068-2-2
Bd
IEC 60870-2-2
IEC 60654-1
C3
C3
Maximum air temperature
for safe operation
3)
55°C
2)
IEC 61010-1
Cyclic damp heat
25/40°C/120 h
95% rH
IEC 60068-2-30
Temperature gradient 30°C/h IEC 60870-2-2
IEC 60654-1
C2
C2
Relative air humidity 5…95% IEC 60870-2-2
IEC 60654-1
C1
C1
Absolute air humidity 35 g/m
3
IEC 60870-2-2
IEC 60654-1
C2
C2
Air pressure
70…106 kPa
(up to 3000 m)
IEC 60870-2-2
IEC 60654-1
C2
C2
Temperature with storage
and transport
-30…+85°C
Pollution degree 2 IEC 61010-1
1)
applies for horizontal mounting
2)
applies for vertical mounting (I/O Modules, Remote I/O interface)
3)
applies for vertical mounting in terms of personal and system safety

Table of Contents

Other manuals for Siemens SICAM A8000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SICAM A8000 Series and is the answer not in the manual?

Siemens SICAM A8000 Series Specifications

General IconGeneral
Modular DesignYes
Operating Temperature Range-40°C to +70°C
Communication InterfaceEthernet, RS485, RS232
Protection ClassIP20
Communication ProtocolsIEC 61850, DNP3, Modbus, IEC 60870-5-104
Power Supply24 V DC, 230 V AC
MountingDIN rail
Digital InputsUp to 32
Digital OutputsUp to 16
Input Voltage Range24 V DC to 230 V AC

Related product manuals