Standard I/O Modules
SICAM A8000 Series, SICAM I/O Modules Unrestricted 51
DC8-012-2.06, Edition 09.2019
Mechanics and Connectors
Terminals Removable screw terminals (grid size 5.08)
Connection data X1, X2, X3, X4
Locking torque
*)
(PHOENIX)
(FCI)
0.5 Nm to 0.6 Nm
0.36 Nm to 0.44 Nm
AWG
min. 22
max. 12
Conductor cross section solid
min. 0.33 mm²
max. 2.5 mm²
Conductor cross section stranded
min. 0.33 mm²
max. 2.5 mm²
Conductor cross section stranded with
ferrule without plastic sleeve
min. 0.33 mm²
max. 2.5 mm²
Conductor cross section stranded with
ferrule with plastic sleeve
min. 0.33 mm²
max. 2.5 mm²
2 wires stranded with ferrule without
plastic sleeve
min. 0.33 mm²
max. 1 m
2 wires stranded with TWIN ferrule with
plastic sleeve
min. 0.5 mm²
max. 1.31 m
Wire strip length
min. 6 mm
max. 7 mm
Length ferrule 10 mm
Dimensions 124 x 30 x 132 mm (L x W x H, dimensions w/o DIN rail)
Weight Approx. 241 g (incl. bus module 12 g)
*)
the respective manufacturer is imprinted at the terminal (see section 1.2.4.1, Screw Terminal Types)

Table of Contents

Other manuals for Siemens SICAM A8000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SICAM A8000 Series and is the answer not in the manual?

Siemens SICAM A8000 Series Specifications

General IconGeneral
Modular DesignYes
Operating Temperature Range-40°C to +70°C
Communication InterfaceEthernet, RS485, RS232
Protection ClassIP20
Communication ProtocolsIEC 61850, DNP3, Modbus, IEC 60870-5-104
Power Supply24 V DC, 230 V AC
MountingDIN rail
Digital InputsUp to 32
Digital OutputsUp to 16
Input Voltage Range24 V DC to 230 V AC