Configuration
4.10 Data points
SIMATIC CC7
106 Operating Instructions, 10/2019, C79000-G8976-C503-02
● Time trigger
For time triggers, select the value of the cycle and the respective unit of time from the
drop-down list.
– Cyclic
The value of the data point is transferred cyclically. Ranges of values:
100 .. 100 000 000 ms
1 .. 1 000 000 s
1 .. 1666 min
1 .. 27 h
– Once daily
The value is transferred once a day at the configured time.
– Once weekly
The value is transferred once a week.
– Once monthly
The value is transferred once a month.
If a month has fewer days than the day specified in the configuration, the value of the
data point is transferred at the end of the month.
●
Value trigger
Select the type using the drop-down list and add the respective values.
The value ranges of the value triggers depend on the data type of the data point.
– Deviation
The value is transferred as soon as it changes compared to the value that was read in
before.
– Area outside
The value is transferred as soon as it is outside the configured area.
– Area within
The value is transferred as soon as it is inside the configured area.
– Threshold HIGH
The value is transferred as soon as it exceeds the configured value.
– Threshold LOW
The value is transferred as soon as it drops below the configured value.
Note:
The range of values of the station data point is converted to the range of values of the
device data point.
●
Input trigger
– Digital input
Transfer once upon edge change at the digital input
Alternatively with edge change 1 → 0 or 0 → 1