EasyManua.ls Logo

Siemens simatic et200sp - Page 41

Siemens simatic et200sp
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Circuit diagram example
4.4 TIA Portal configuration
Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram
Function Manual, 08/2020, A5E44991382002A/RS-AB/002
41
Finally, the F-DQ module is configured to control the redundant contactors. Here again, the
F parameters remain unchanged (default setting). The setting of the safe monitoring can be
taken from the following figure.
Figure 4-16 Configuration of the F-DQ module
Note
Unused channels, such as channels 1 to 3 of the F
-DQ module, should be deactivated for
reasons of clarity and improved performance. For this purpose, the check is removed from
"Activated" for the
corresponding channels. For the F-CM AS-i Safety ST module, the user
must activate the input channels required for the configured AS-i slaves.

Other manuals for Siemens simatic et200sp

Related product manuals