FM 351 Positioning Function Module
EWA 4NEB 720 6001-02
To wire the front connector, proceed as follows:
1. Strip 6 mm (0.25 in) from the wire, fitting a wire end ferrule if required.
2. Open the front door, bring the front connector to the wiring position.
3. Fit the strain relief to the connector.
4. If you bring out the wires downwards, begin the wiring from below, other-
wise at the top. Also screw down terminals which are not used.
The tightening torque is 60 Ncm to 80 Ncm.
5. Pull the strain relief for the cable tree.
6. Push the front connector into the operating position (pressing the locking
element).
7. You can fill in the enclosed label and insert it into the front door.
Note
No shielded cables are required when wiring the digital inputs and outputs
up to the following cable lengths:
Digital inputs: max. 100 m (110 yds)
Digital outputs: max. 100 m (110 yds)