Wiring
4-16
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
Power from the drive unit
Figure 4-8 shows examples of how to power the standby signal from the drive unit.
FM 353
RM_P
RM_N
L+
M
19
9
10
20
X1
RM_P
RM_N
L+
M
19
9
10
20
X1
M
M
P24
P24
Power section
Actuation, current-sourcing
Actuation, current-sinking
Fig. 4-8 Actuation of the input controller message, power supply from the
drive unit
4 digital outputs (DQ1...4)
All outputs have equal priority. The switching function is allocated to the output
number in machine data (seeMD34, 35, Section 5.3.1).
These four outputs are intended for wiring of application-specific signals.
Possible uses include:
S Position reached and stopped
S Switching function M command
S Forward/backward rotation
See Section 5.3.1 for further applications.
Note
Make sure that the cable length between the digital outputs and the load does not
exceed a permissible max. length of 30 m.