Service and maintenance
8.2 Error messages
SIMATIC RF360R
Configuration Manual, 03/2022, C79000-G8976-C629-02
91
8.2.3 XML error messages
A list of the possible XML error codes can be found in the "XML programming for SIMATIC
Ident (https://support.industry.siemens.com/cs/ww/en/view/109781631)" manual.
8.2.4 OPC UA error messages
The following table lists the OPC UA-specific error codes.
Table 8- 5 OPC UA error messages of the communication module / reader
AutoId
OPC UA
AutoId
Error description
TOTAL
• Firmware error
Possible cause: The firmware update was not run
completely.
• Internal communications error of the communications
module/reader
– Connector contact problem on the communications
module / reader
– Hardware of the communications module/reader has a
defect; → Send in communications module/reader for
repair
– Start "INIT" after correcting the error
• Internal monitoring error of the communications
module/reader
– Program execution error on the communications module
/ reader
– Turn the power supply of the communications
module/reader off and on again
–
Start "INIT" after correcting the error
The "Inventory" command failed.
Enabling write protection on the transponder has failed.
The "Kill" command failed.
The transponder is read/write-protected.
The transponder password is incorrect. Access is denied.
Invalid
Argument /
good
FOUND_ERROR
A parameter of an OPC UA command has an invalid value.
"ReadTag"/"WriteTag" command:
The addressed memory area is not available in the current