Service and maintenance
8.2 Error messages
SIMATIC RF360R
92 Configuration Manual, 03/2022, C79000-G8976-C629-02
AutoId
status
OPC UA
status
AutoId
text
Error description
7
good
OUT_OF_RANGE_
ERROR
Address error
The address range of the transponder has been exceeded.
Possible causes:
Start address of the command start has been incorrectly set.
Wrong transponder type
The area to be written to is write-protected.
7
good
OUT_OF_
RANGE_ERROR
The requested data is not available.
8
good
NO_
IDENTIFIER
There is no transponder with the required EPC ID/UID in the
transmission window or there is no transponder at all in the
antenna field.
9
good
MULTIPLE_
IDENTIFIERS
More transponders are located in the transmission window than
can be processed at the same time by the reader.
9
good
MULTIPLE_
IDENTIFIERS
There is more than one transponder in the transmission
window.
10
good
READ_
ERROR
Read access to the transponder has failed.
14
good
WRITE_
ERROR
Write access to the transponder has failed.
14
good
WRITE_
ERROR
Writing the EPC ID/UID on the transponder has failed.
15
good
NOT_SUPPORTED_
BY_DEVICE
Unknown command
An uninterpretable XML command was sent to the reader or the
Ident profile sends an uninterpretable command to the reader.
Possible causes:
The "AdvancedCmd" block was supplied with an incorrect
"CMD".
The "CMD" input of the "AdvancedCmd" block was
overwritten.
17
good
DEVICE_NOT_
READY
The specified read point is not active because no antenna was
assigned to it.
18
good
INVALID_
CONFIGURATION
The specified tag field of the transponder is unknown.
19
good
RF_COMMUNICATION_
ERROR
The transponder is not responding.
19
good
RF_COMMUNICATION_
ERROR
The verification of the written transponder data has failed.
19
good
RF_COMMUNICATION_
ERROR
General transponder error
19
good
RF_COMMUNICATION_
ERROR
The transponder has too little power to execute the command.
19
good
RF_COMMUNICATION_
ERROR
The transponder signals a CRC error.
19
good
RF_COMMUNICATION_
ERROR
The selected frequency is not enabled.
19
good
RF_COMMUNICATION_
ERROR
The carrier signal is not activated.
19
good
RF_COMMUNICATION_
ERROR
General radio protocol error