Service and maintenance
8.2 Error messages
SIMATIC RF360R
Configuration Manual, 03/2022, C79000-G8976-C629-02
93
AutoId
status
OPC UA
status
AutoId
text
Error description
20
good
DEVICE_FAULT
Fault in power supply
The power supply is very close to the low limit.
20
good
DEVICE_FAULT
Antenna errors
The antenna or the antenna cable is defective.
Error in the connection to the reader; the reader is not
answering (in PROFIBUS operation).
The cable between the communications module and
reader is wired incorrectly or there is a cable break
The 24 V supply voltage is not connected or is turned off
or has failed briefly
Automatic fuse on the communications module has
blown
Hardware defective
Another reader is in the vicinity and is active
There is a reflecting metal surface in the vicinity that is
disrupting the antenna field
Execute "init_run" after correcting the error
--
--
--
The selected antenna is not enabled.
--
OpcUa_
BadInvalidS
tate
--
The command is not permitted in this status or is not supported.
Possible cause:
"INIT" was chained.
Command repetition was started without "Presence mode".
--
OpcUa_
BadOutOf
Range /
OpcUa_
Bad
Configurati
on
Error
--
No or bad configuration data/parameters were transferred.
Possible cause:
You are accessing a read point that is not configured.
--
BadInvalid
Argument
--
A parameter is missing.
--
BadInvalid
Argument
--
The parameter has an invalid format.
--
BadInvalid
Argument
--
The parameter type is invalid.
--
BadInvalid
Argument
--
Unknown parameter.
--
Bad
--
The command or the frame has an invalid format.