Service and maintenance
8.2 Error messages
SIMATIC RF360R
Configuration Manual, 03/2022, C79000-G8976-C629-02
93
AutoId
OPC UA
AutoId
Error description
Fault in power supply
The power supply is very close to the low limit.
• The antenna or the antenna cable is defective.
• Error in the connection to the reader; the reader is not
answering (in PROFIBUS operation).
– The cable between the communications module and
reader is wired incorrectly or there is a cable break
– The 24 V supply voltage is not connected or is turned off
or has failed briefly
– Automatic fuse on the communications module has
blown
– Hardware defective
– Another reader is in the vicinity and is active
– There is a reflecting metal surface in the vicinity that is
disrupting the antenna field
–
Execute "init_run" after correcting the error
The selected antenna is not enabled.
BadInvalidS
tate
The command is not permitted in this status or is not supported.
Possible cause:
• "INIT" was chained.
• Command repetition was started without "Presence mode".
BadOutOf
Range /
OpcUa_
Bad
Configurati
on
No or bad configuration data/parameters were transferred.
Possible cause:
• You are accessing a read point that is not configured.
The parameter has an invalid format.
The parameter type is invalid.
The command or the frame has an invalid format.