S5-115F Manual   Technical Specifications
Digital Output Module 8 x 115 to 230 V AC; 2 A, Floating, Safety-Related (6ES5 456-7LB11)
L1
Technical Specifications
Number of outputs 8
Floating yes (optocoupler)
-  in groups of 1
Load voltage L1
-  rated value 115 to 230 V AC
-  frequency 47 to 63 Hz
-  permissible range 89 to 264 V
Output voltage
-  at ”1” signal min. L1 - 7 V
Output current
at ”1” signal
-  rated value 2 A
-  permissible range 40 mA to 2 A
-  lamp load 50 W
Leakage current
at ”0” signal  typ. 3 to 5 mA
1
Parallel connection  of
outputs not possible
Making capacity depends on the fuse
Permissible total current
of outputs 100%
Short-circuit protection 4 A FF fuse 
(for each group) (e.g., Wickmann 19231)
Fault indication defective fuse
(red LED for each group)
Switching frequency max. 10 Hz
Cable length
-  shielded max. 1000 m (3281 ft.)
-  unshielded max. 300 m (984 ft.)
Insulation rating to VDE 0160
Rated insulation voltage
(between groups) 250 V AC
-  insulation group C
-  tested with 2700 V AC
Rated insulation voltage
(L1 to ) 250 V AC
-  insulation group C
-  tested  with 2700 V AC
Current consumption 
-  from 5 V (internal) max. 35 mA
Power losses of 
the module typ. 16 W
Weight approx. 1.1 kg (2.43 lb.)
1 Please note the drop-out current of the connected loads
(relays of the range 3TJ1 to 3TJ5 and relays of the
SIMICOMT range cannot be driven)!
Terminal assignment
Simplified schematic 
B
U
S
~
N
DIGITAL
OUTPUT
8x115/230V DC
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
6ES5 456-7LB11
N
~
L1
N
~
L1
N
~
L1
N
~
L1
N
~
L1
N
~
L1
N
~
L1
N
~
L1
EWA 4NEB 811 6148-02
8-17