Technical Specifications S5-115F Manual
Relay Output Module for Measuring Currents 16 x 24 V DC, Reaction-Free (6ES5 458-7LA11)
+
+
M ext.
Technical Specifications
Number of outputs 16
- contact bridge no
- floating yes
- isolated in groups of 1
- relay type 3700-2501-011
(Günther)
Limiting continuous current
per contact 0.5 A
Parallel connection of
outputs possible
Permissible total current
of outputs 100%
Switching frequency
- inductive load max. 100 Hz
- resistive load not permissible
Switching voltage max. 30 V DC
Switching capacity of
the contacts
- resistive load 10 W at 0.5 A
- inductive load not permissible
Number of contact
operating cycles
according to VDE 0660,
Part 200
- DC 11 1 x 10
9
Supply voltage L +
(for relay)
- rated value 24 V DC
- permissible range 20 to 30 V
- surge voltage at t < 0.5 sec. 35 V
- ripple max. 3.6 V
Cable length
- shielded 1000 m (3281 ft.)
- unshielded 300 m (984 ft.)
Insulation rating to VDE 0160
Rated insulation voltage
(between contacts) 30 V DC
- insulation group C
- tested with 500 V AC
Rated insulation voltage
(contacts to L +) 30 V DC
- insulation group C
- tested with 500 V AC
Rated insulation voltage
(contacts to ) 30 V DC
- insulation group C
- tested with 500 V AC
Current consumption
- from 5 V (internal) max. 50 mA
- from L + (for relay) 240 mA
Power losses of
the module typ. 5 W
Weight approx.0.8 kg (1.76 lb.)
Terminal assignment
Simplified schematic
L+ Aux.
B
U
S
M
DIGITAL
OUTPUT
16x24VDC Relay
6ES5 458-7LA11
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
8-18
EWA 4NEB 811 6148-02