S5-115F Manual   Technical Specifications
Relay Output Module 8 x 30 V DC / 60 V AC, Safety-Related (6ES5 458-7LB11)
+
+
L+(Aux.)
Switching
voltage
Technical Specifications
Number of outputs 8
-  contact bridge varistor
SIOV-S07-K275
-  floating yes
-  isolated in groups of 1
-  relay type V23157-006-A402
(Siemens)
Limiting continuous current
per contact 5 A
Parallel connection of
outputs possible
Permissible total current
of outputs 100%
Switching capacity of
the contacts
-  resistive load 5 A at 250 V AC
2.5 A at 30 V DC
-  inductive load 1.5 A at 250 V AC
0.5 A at 30 V DC
Switching voltage is limited to 60 V AC in the S5-115F
Switching frequency max. 10 Hz
Number of contact
operating cycles
according to VDE 0660,
Part 200
-  AC 11 1.5 x 10
6
-  DC 11 0.5 x 10
6
Supply voltage L+
(for relay)
-  rated value 24 V DC
-  permissible range 20 to 30 V
-  surge voltage at t 0.5 s 35 V
-  ripple max. 3.6 V
Insulation rating to VDE 0160
Rated insulation voltage 
(between contacts) 250 V AC
-  insulation group C
-  tested with 1500 V AC
Rated insulation voltage
(contacts to L+) 250 V AC
-  insulation group C
-  tested with 1500 V AC
Rated insulation voltage
(contacts to )  250 V AC
-  insulation group C
-  tested with 1500 V AC
Current consumption
-  from 5 V (internal) max. 50 mA
-  from L+ (for relay) 200 mA
Power losses of
the module typ. 4 W
Weight approx. 0,8 kg (1.76 lb.)
Terminal assignment
Simplified schematic
M ext.
B
U
S
 
DIGITAL
OUTPUT
8x60VUC Relay
6ES5 458-7LB11
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
M
M
 
 
 
 
 
 
 
 
EWA 4NEB 811 6148-02