7.19 Hot plugging
SIMOTION D410-2 is capable of hot plugging, i.e. SIMOTION D410-2 can be unplugged or
plugged in again to the PM340/PM240‑2 energized.
The following scenarios are therefore possible:
SIMOTION D410-2 is supplied with power via X124, Power Module is de-energized
SIMOTION D410-2 is de-energized, Power Module is energized
SIMOTION D410-2 is supplied with power via X124, Power Module is energized
Unplugging and plugging of a SIMOTION D410-2 is only permitted on one and the same Power
Module. If the SIMOTION D410-2 is plugged into a different Power Module (power, type, article
number, serial number), then alarm 30074 is issued on the drive side.
SIMOTION D410-2 must always be supplied via X124 for operation. There is no warm restart
when plugged in again.
If the SIMOTION D410-2 is unplugged from the Power Module, a drive connected to the Power
Module stops.
Commissioning (software)
7.19 Hot plugging
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015 247