Procedure
1. Specify whether the external signal is received via a fast digital input (probe) or from another
source, e.g. via the eldbus.
2. To initiate a block change via the machine control system, you must interconnect this signal
with a signal of your choice.
3. Select the input with which cam signal 1 is interconnected.
4. Select the input with which cam signal 2 is interconnected.
5. Specify the edge with which the converter jumps to the next traversing block:
0: Rising edge
1: Falling edge
You have now dened an external signal for the block change.
❒
Parameter Meaning
p0488 Probe 1, input terminal
p0489 Probe 2, input terminal
p0581 Probe edge
0 Positive edge 0 → 1
1 Negative edge 1 → 0
p2584 Conguration functions
.0
0
1 signal: activates position feedback signal (p2688 and r2689)
Commissioning
6.8 Traversing blocks
Basic positioner
Function Manual, 09/2020, FW V4.7 SP13, A5E34257659B AG 79